RELAY OVERLOAD 3P 600V 10A CLASS 63-80A SETTING RANGE

SCH-LRD3363 MFG #: LRD3363
$0.00 /
  • Amperage: 10
  • Best Seller: False
  • Country Origin: FR
  • Dangerous Goods: False
  • Device Type: Overload Relay
  • Discontinued: False
  • Featured Product: False
  • Green Product: False
  • Limited Quantity: False
  • Made in Canada: False
  • Manufacturer: SCHNEIDER ELECTRIC
  • Manufacturer Category: TE3D-30507
  • Manufacturer Product Code: 20833
  • Mfr Vendor ID: 599
  • Oversize product: False
  • Poles: 3
  • Restricted Delivery: False
  • SPF Product ID: 141904
  • Unit of Measure: E
  • UPC: 785901208334
  • Voltage: 600
  • Web Group: 1020901000000
TeSys LRD thermal overload relay, 80A/1000V, thermal setting range 63-80A, tripping class 10A, for protection of 3-phase motors 37kW@400V. Differential device with phase failure and load unbalance detection. It provides a thermal adjustement dial, a manual-automatic reset selector acting also as reset button, a trip test button for simulation of a tripping, a stop button, a flag indicator and 2 auxiliary contacts 1NO+1NC for fault signalling. Settings are protected by a transparent cover lockable by sealing. Connection by screw clamp terminals, it connects directly to the bottom terminals of 3-pole contactors LC1D80-D95. Mounting on DIN rail or screw fixing, separated from the contactor, with use of a terminal block LA7D3064 (to be ordered separately). Multi standards certified (IEC, UL, CSA, CCC, EAC, ATEX, Marine), Green Premium compliant (RoHs/Reach).